Arcing Fault Current and the Criteria for Setting Ground Fault Relays in Solidly-Grounded Low Voltage Systems

Abstract:

In the 1960′s numerous damages were documented on 480V, 3-phase, 4-wire power systems due to arcing ground faults. To alleviate this problem, the National Electrical Code (NEC) now requires ground fault protection in low voltage switchgear with continuous current ratings above 1,000A and operating at more than 150V phase-to-ground on solidly-grounded systems. However, burn down damage and personal injury continues to occur. This paper provides a simplified technique to accurately estimate this arcing fault current, and discusses its effects on the settings of relays and interrupting devices utilized in low voltage systems. It suggests that the criteria for setting the ground fault sensing devices should be changed to accommodate the maximum allowable exposure of personnel to arc flashes that may occur in the system. This is a much stricter guideline than that currently required by the NEC.

Author: Keith Malmedal , P.K. Sen
Where Published:  I&CPS Conference Record 2000
When Published: 2000

Download the full text:

Arcing Fault Current and the Criteria for Setting Ground Fault Relays in Solidly-Grounded Low Voltage Systems

Technical Publications

  • Application of Out-of-Step Relaying for Small Generators in Distributed Generation
  • The Grounding of Power Systems Above 600 Volts: A Practical View Point
  • Structural Loading Calculations Of Wood Transmission Structures
  • System Grounding and Ground-Fault Protection in the Petrochemical Industry: A Need for a Better Understanding
  • Steel Grounding Design Guide and Application Notes
  • A Better Understanding of Harmonic Distortion in the Petrochemical Industry
  • Arcing Fault Current and the Criteria for Setting Ground Fault Relays in Solidly-Grounded Low Voltage Systems
  • Some Lessons Learned From Commissioning Substation and Medium Voltage Switchgear Equipment
  • High-Resistance Grounding of Low-Voltage Systems: A Standard for the Petroleum and Chemical Industry
  • Basics and Advances in Battery Systems
  • Power Systems in Close Proximity to Pipelines
  • A Cathodically Protected Electrical Substation Ground Grid
  • Use of the National Electrical Safety Code in the Petro-Chemical Industry
  • High Altitude Considerations of Electrical Power Systems and Components

Recommended Links

  • ASCE
  • IEEE IAS
  • IEEE IAS PCIC

Contact Us

  • Contact Us
  • Careers

Search

Meta

  • Log in
  • Entries RSS
  • Comments RSS
  • WordPress.org

All Rights Reserved. © NEI Electric Power Engineering, Inc.
PO Box 1265, Arvada, CO 80001 | 303-431-7895